Size the breaker at 125 percent of the charger's continuous output. A 32 amp charger goes on a 40 amp breaker, a 40 amp charger on a 50 amp breaker, and a 48 amp charger on a 60 amp breaker. The wire has to be rated for that breaker too, so the charger, breaker and wire are chosen together, not one at a time.
Get Your EV Charger Circuit Sized RightHere are the setups we install most often in Brighton and Denver garages. A 32 amp charger on a 40 amp, 240 volt circuit adds roughly 25 to 30 miles of range per hour. A 48 amp charger, such as a Tesla Wall Connector set to full output, runs on a 60 amp circuit and adds up to about 44 miles of range per hour on cars that can accept 48 amps. Hardwired installs are needed above 40 amps. Plug in chargers on a NEMA 14-50 outlet are limited to 40 amps on a 50 amp circuit.
The right breaker is the one your panel can support. On a 100 amp service, a 40 amp circuit for a 32 amp charger often fits when a 60 amp circuit would not. Many cars cannot even accept more than 32 to 40 amps on AC charging. A load calculation tells you the largest size your home can carry safely.
A Level 2 circuit needs a dedicated 240 volt breaker, correctly sized copper wire, and GFCI protection where code requires it. It also needs a permit and inspection through the City of Brighton, Adams County, Weld County or Denver, depending on your address. A breaker, wire or charger setting that does not match is a common reason a DIY charger install fails inspection or trips.